Apollo Steam Modulator

Features

  • Linear constant flow technology
  • Instant prime
  • Highly efficient: 99 + efficiency
  • Protects system from water hammer
  • Built with precision machine shop tolerances and specifications long overdue for the HVAC industry
  • Excellent reliability and long life under extreme conditions
  • Simple to inspect and service
  • The modern method to blend existing steam principles with high tech manufacturing
  • Operating on a close approach flow limit principle
    – Continuously modulates with an effective range of 15″ vacuum to 300 psi steam

Applications

  • Steam Tracing
  • Sterilizers
  • Drip legs
  • Cooking Equipment
  • Plating Tanks
  • Tire Presses
  • Air Vents
  • Unit Heaters
  • Laundry Equipment
  • Process Equipment
  • Radiators
  • Optional Modulating Orifice Technology

Specifications

TA-Apollo-1001 NPT M1 NPT FM1 Union5-1/81-3/4 Dia.3-1/2

Model No. Pipe Size IN Pipe Size OUT A B C D
(less union)
TA-Apollo-50 1/2 NPT M 1/2 NPT FM 1/2 Union 4-21/32 1-3/4 Dia. 3-15/32
TA-Apollo-75 3/4 NPT M 3/4 NPT FM 3/4 Union 4-27/32 1-3/4 Dia. 3-1/2
TA-Apollo-125 1-1/4 NPT M 1-1/4 NPT FM 1-1/4 Union 6-1/8 2-1/4 Dia. 4-1/2
TA-Apollo-HC-200
(HC only)
2 NPT M 2 NPT FM 2 Union 6-3/4 3 Dia. 4-3/4

Working Capacity

Model No. Differential Pressure PSIG
1.0 2.0 5.0 10 15 30 70 100 125 150 200 250
TA-Apollo-50 148 208 330 470 570 750 1240 1480 1650 1810 2090 2340
TA-Apollo-75
TA-Apollo-100
TA-Apollo-125
Model No. High Capacity – Differential Pressure PSIG
1.0 2.0 5.0 10 15 30 70 100 125 150 200 250
TA-Apollo-HC-50 1320 1870 2950 4170 5110 7230 10920 12720 14040 15240 17410 19320
TA-Apollo-HC-75
TA-Apollo-HC-100
TA-Apollo-HC-125
TA-Apollo-HC-200